HOME | PRODUCTS
ADVANCED FEATURES
- It controls three phases of current, voltage and three temperature inputs.
- Potential measurement (measurement of a voltage phase).
- Statistical data of the last 10 shots, with date and time stamp.
- RTD compensation for thermal overload.
- Multiple thermal overload curves.
- Pre-alarm too many starts, configurable to an output relay.
- Capture and indication of the minimum and maximum RMS values, average of the three phases of current, voltage, minimum and maximum frequency.
- Independent configuration of ground fault during startup.
- Modbus communication.
- Six programmable discrete inputs and outputs.
FULL PROTECTION PACKAGE
- Communication fault / internal fault (3).
- Low voltage (27).
- Low power levels 1 and 2 (32L / R).
- Low current levels 1 and 2 (37).
- Over temperature of the bearing (38).
- Current imbalance levels 1 and 2 (46).
- Phase sequence (47).
- Maximum start time (48).
- Over temperature RTD (49T).
- High temperature levels 1 and 2, sensors 1-10 (49R).
- Thermal capacity level 1 (49/51).
- Over current level 2, short (50).
- Ground fault during start (50G).
- Ground fault levels 1 and 2 (50G / N).
- Increased load, alarm (51L).
- Overcurrent level 1, jam (51R).
- Low delayed / leading power factor (55).
- Over voltage levels 1 and 2 (59).
- Too many starts (66).
- Welded contactor (MPS 3000C) (74).